Air Pressure Control Valves and Air Pressure Stabilisers

Protecting individual doors

The protection mechanism for individual doors is examined below based upon the assumption that only one door is open at any time. Within the overall supply volumes available it is not possible to provide protection for more than one open door at a time.

Anaesthetic - Corridor door open

Double door - Required flow 0.57 m3/s. (Clean) - (Transitional)

Opening this door causes the pressure in the Anaesthetic to fall from 14 Pa to 3 Pa (i.e. common pressure with the Corridor). The door leakage from the Theatre to Anaesthetic door increases to 0.1 m3/s and the stabiliser between Theatre and Anaesthetic has to be able to pass 0.47 m3/s (@ 22 Pa differential) to give the required flow of 0.57 m3/s across the open doorway.